This standard is based on the 2000 Kentucky Fire Prevention Code that references NFPA 30 and NFPA 45. University laboratories are classified as a Class B (Moderate Fire Hazard) and the following listed quantities comply with that classification.
- The total amount of solvents within the laboratory shall not exceed ten (10) gallons per 100 sq.ft.
- The total amount of unprotected solvents within the laboratory shall not exceed (see definitions) five (5) gallons per 100 sq.ft.
- Solvents in excess of the amounts listed in item #1 shall be in an inside (bulk) storage rooms meeting NFPA 30.
- Flammable solvents (i.e., flash point < 100°F) must not be stored in an ordinary refrigerator. Must use an explosion proof refrigerator or flammable safe refrigerator.
Lab size (gross ft2) | Total Solvent Volume Allowed (gal) (based on 10 gal/100ft2) | Unprotected Solvent Volume Allowed (gal) (based on 5 gal/100ft2) |
---|---|---|
400 | 40 | 20 |
500 | 50 | 25 |
100 | 10 | 5 |